Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T09CM01206
Parcel: 140260370

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T09CM01206
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revisions to the project drawings shall be made to full-size copies of the approved plans.
2. The revised water calculations show 3.5 fixture units for each water closet as the basis for reducing the size of the water meter and some of the water pipes. Per Table A-2, UPC 2006, a flush valve water closet for public use requires 5.0 fixture units. Submit an appeal to the building official and provide calculations (e.g. a Monte Carlo simulation of fixture use, assuming a failure rate of less than 1%) to justify the reduced fixture units. Reference: Sections 301.2, 610.3, and 610.5, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2009 DELMA ROBEY OUT TO CUSTOMER Completed
10/28/2009 SUE REEVES REJECT SHELF Completed