Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/26/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revisions to the project drawings shall be made to full-size copies of the approved plans. 2. The revised water calculations show 3.5 fixture units for each water closet as the basis for reducing the size of the water meter and some of the water pipes. Per Table A-2, UPC 2006, a flush valve water closet for public use requires 5.0 fixture units. Submit an appeal to the building official and provide calculations (e.g. a Monte Carlo simulation of fixture use, assuming a failure rate of less than 1%) to justify the reduced fixture units. Reference: Sections 301.2, 610.3, and 610.5, UPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/28/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
10/28/2009 | SUE REEVES | REJECT SHELF | Completed |