Permit Number: T09CM01205
Parcel: 13707044A

Address:
5201 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01205
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/01/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. The ventilation calculations indicate that the building uses only evaporative coolers.
Show how the building complies with Section 309.1, IMC 2006.