Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01205
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/22/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. CHANGES HAVE BEEN MADE TO SHEET A1, AND A NEW SHEET INSERTED INTO THE DRAWING SET. CLARIFY THE PLAN ON THE WEST SIDE OF THE BUILDING (AROUND THE MOP SINK). THIS IS A REVISION TO AN APPROVED SHEET. |
| 05/22/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/22/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The ventilation calculations indicate that the building uses only evaporative coolers. Show how the building complies with Section 309.1, IMC 2006. |
| 05/22/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |