Permit Number: T09CM01205
Parcel: 13707044A

Address:
5201 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01205
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/22/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. CHANGES HAVE BEEN MADE TO SHEET A1, AND A NEW SHEET INSERTED INTO THE DRAWING SET. CLARIFY THE PLAN ON THE WEST SIDE OF THE BUILDING (AROUND THE MOP SINK). THIS IS A REVISION TO AN APPROVED SHEET.
05/22/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/22/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The ventilation calculations indicate that the building uses only evaporative coolers. Show how the building complies with Section 309.1, IMC 2006.
05/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved