Permit Number: T09CM01205
Parcel: 13707044A

Address:
5201 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01205
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2009 DAVID RIVERA ZONING REVIEW Approved
05/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations for the kitchen. Reference: Section 403.3 and 508.1, IMC 2006; see also footnotes f and g, Table 403.3, IMC 2006.
2. Clarify the reason for the backdraft damper in the exhaust fans.
3. Provide constuction information for the wall adjacent the the hoods. Reference: Section 507.9, IMC 2006.
05/13/2009 DSANTAC2 ELECTRICAL-COMMERCIAL REVIEW Denied Project; 5201S. 12TH. AV.
T09CM01205


1. Panel LD, clarify removed circuits if panel is new.
2. Indicate riser conduit size and service entrance conducters.
3.What circuits and panels used for hood controls.

Dan Santa Cruz
City of Tucson DSD
Electrical Plan Check
5-13-09
05/13/2009 ROBERT SHERRY WATER REVIEW Approved
05/13/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/13/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
05/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the size of the branch gas pipe serving G-1.
05/13/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
05/13/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
05/13/2009 ERIC NEWCOMB ADA REVIEW Passed
05/14/2009 DAVE MANN FIRE REVIEW Approved
05/22/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2009 DELMA ROBEY OUT TO CUSTOMER Completed