Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01205
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2009 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/13/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations for the kitchen. Reference: Section 403.3 and 508.1, IMC 2006; see also footnotes f and g, Table 403.3, IMC 2006. 2. Clarify the reason for the backdraft damper in the exhaust fans. 3. Provide constuction information for the wall adjacent the the hoods. Reference: Section 507.9, IMC 2006. |
| 05/13/2009 | DSANTAC2 | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project; 5201S. 12TH. AV. T09CM01205 1. Panel LD, clarify removed circuits if panel is new. 2. Indicate riser conduit size and service entrance conducters. 3.What circuits and panels used for hood controls. Dan Santa Cruz City of Tucson DSD Electrical Plan Check 5-13-09 |
| 05/13/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/13/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/13/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 05/13/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the size of the branch gas pipe serving G-1. |
| 05/13/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 05/13/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Passed | |
| 05/13/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 05/14/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/22/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/22/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |