Permit Number: T09CM01201
Parcel: 14118002C

Address:
9800 E RITA RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM01201
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2009 DAVE MANN FIRE REVIEW Approved
05/13/2009 GERRY KOZIOL WWM REVIEW Passed
05/13/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/14/2009 RONALD BROWN ZONING HC SITE REVIEW Passed PROJECT IS A COT OWNED AND OPERATED PROPERTY REFERENCE ADA SITE ZONING COMMENTS
05/14/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural foundation details on the drawings for both light poles.
2. Provide a letter of deferred submittal for the ramada to the building official .
3. Provide connection detail of cmu column cap to ramada steel beam.
4. At detail 4/A6, calculations specify 3,000 psi concrete for foundations while the note here refers to 2,500 psi. Please clarify.
5. Provide for a speciasl inspection for anchor bolts in concrete.

End of Review
05/15/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Purple Heart Park - New Ball Field
T09CM01201
Building Plan (1st Review)

TRANSMITTAL DATE: May 18, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan.. Please submit two copies of the approved and stamped site plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm01201.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
05/22/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved
05/22/2009 RMYERS1 WATER REVIEW Approved
06/01/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/02/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/08/2009 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/01/2009 CPIERCE1 OUT TO CUSTOMER Completed