Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01190
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/04/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vent for the flow control device for the 3-compartment sink. Reference: Section 1014.2.1, UPC 2006. 2. Provide a vented trap for the 3-compartment sink. 3. "Sure Seal" trap protectors are not approved for use in the City of Tucson. 4. The specified grease trap has a 3" outlet; reduction of the outlet to 2" is not permissible. Reference: Section 316.4.1, UPC 2006. 5. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length. Reference: Section 707.4, UPC 2006. 6. Show the point of connection of the 1-1/2" waste line from the hand sink located in the scullery area on Stack B. |
06/04/2009 | DROBEY1 | WWM | REVIEW | Needs Review |