Permit Number: T09CM01190
Parcel: 117121280

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01190
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vent for the flow control device for the 3-compartment sink. Reference: Section 1014.2.1, UPC 2006.
2. Provide a vented trap for the 3-compartment sink.
3. "Sure Seal" trap protectors are not approved for use in the City of Tucson.
4. The specified grease trap has a 3" outlet; reduction of the outlet to 2" is not permissible. Reference: Section 316.4.1, UPC 2006.
5. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length. Reference: Section 707.4, UPC 2006.
6. Show the point of connection of the 1-1/2" waste line from the hand sink located in the scullery area on Stack B.
06/04/2009 DROBEY1 WWM REVIEW Needs Review