Permit Number: T09CM01102
Parcel: 11505169B

Address:
114 E RILLITO ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01102
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2010 GERRY KOZIOL WWM REVIEW Denied NO STRUCTURES OR LANDSCAPING OF ANY KIND ALLOWED IN EXSISTING PUBLIC SEWER EASEMENT OR OVER EXSISTING PUBLIC SEWER I-14-039. D. WILLHOIT RWRD 740-6779
NEED FLOOR PLAN OF METAL BUILDING SHOWING PLUMBING FIXTURES FOR SEWER CONNECTION PER CALCULATION. SEE ATTACHED LETTER
04/23/2010 SREEVES1 FIRE REVIEW Passed
04/23/2010 STEVE SHIELDS ZONING REVIEW Approved
04/23/2010 DAVE MANN FIRE REVIEW Denied The design professional must determine the following. A Fire Protection Engineer can be used if necessary.

Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
04/27/2010 JASON GREEN ENGINEERING REVIEW Approved
05/03/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied With the addition of the stairs and ramps on the West side of the proposed metal building please provide the folloeing
1. Structural details of all new retaining walls, stairs, ramps and handrails
2. Structural calculations
3. Project valuation
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
05/04/2010 SUE REEVES REJECT SHELF Completed