07/24/2009 DAVE MANN FIRE REVIEW Denied The design professional must determine the following. A Fire Protection Engineer can be used if necessary.

Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
07/24/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/27/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 114 E. Rillito Street
T09CM01102
Building Plan (2nd Review)

TRANSMITTAL DATE: July 27, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm01102.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
07/29/2009 GERRY KOZIOL WWM REVIEW Denied NO STRUCTURES OR LANDSCAPING OF ANY KIND ALLOWED IN EXSISTING PUBLIC SEWER EASEMENT OR OVER EXSISTING PUBLIC SEWER I-14-039. D. WILLHOIT RWRD 740-6779
NEED FLOOR PLAN OF METAL BUILDING SHOWING PLUMBING FIXTURES FOR SEWER CONNECTION PER CALCULATION. SEE ATTACHED LETTER
08/12/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
08/20/2009 SUE REEVES REJECT SHELF Completed