Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01079
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/07/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/15/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
05/21/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Detail 1/S-1 does not show sufficient detail connections of unistruct to TJI's and of hood support rods to unistrut. |
06/02/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. If the building energy compliance is not in accordance with ASHRAE 90.1, the duct insulation shall be determined by Section 503.2.7, IECC 2006, as amended by the City of Tucson. Reference: Section 501.2, IECC 2006, as amended by the City of Tucson. 2. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. 3. The use of ASHRAE Standard 62.1-2004 for ventilation calculations for multiple-zone systems supplied by a single air handler requires the use of the calculations covered by Section 6.2.5, ASHRAE Standard 62.1-2004 to determine the design outdoor air intake. ASHRAE Standard 62.1-2004 does not appear to include a calculation method for determining the minimum ventilation quantities for multiple-zone systems supplied by multiple air handlers. 4. Provide information regarding the construction of the wall adjacent to the grease hood. Reference: Section 507.9, IMC 2006. 5. The new hood exhausts 4,400 CFM but the evaporative cooler supplies only 3,520 CFM. Where is the additional required 880 CFM of make up air coming from? Reference: Section 508.1, IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/03/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
06/03/2009 | SUE REEVES | REJECT SHELF | Completed |