Permit Number: T09CM01079
Parcel: 12108001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01079
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2009 DAVID RIVERA ZONING REVIEW Approved
05/01/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
05/01/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/01/2009 ROBERT SHERRY WATER REVIEW Approved
05/01/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE CALCULATIONS FOR ADEQUACY OF EXISTING ROOF JOISTS UNDER NEW HOOD LOAD.
2. SHEET S1; DETAIL 1: PROVIDE NOTE ON CONNECTION OF UNISTRUT TO ROOF JOISTS, AND CONNECTION OF HOOD SUPPORT ROD TO UNISTRUT.
05/01/2009 PAUL MACHADO ENGINEERING REVIEW Approved
05/01/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/01/2009 DAVE MANN FIRE REVIEW Approved
05/01/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
05/01/2009 ERIC NEWCOMB ADA REVIEW Passed
05/04/2009 CAGUILA1 WWM REVIEW Needs Review
05/04/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review