Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01079
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2009 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/01/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/01/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/01/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/01/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE CALCULATIONS FOR ADEQUACY OF EXISTING ROOF JOISTS UNDER NEW HOOD LOAD. 2. SHEET S1; DETAIL 1: PROVIDE NOTE ON CONNECTION OF UNISTRUT TO ROOF JOISTS, AND CONNECTION OF HOOD SUPPORT ROD TO UNISTRUT. |
| 05/01/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/01/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/01/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/01/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Passed | |
| 05/01/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 05/04/2009 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 05/04/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |