| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 05/21/2009 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 05/21/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Needs Review | |
| 05/21/2009 | CPIERCE1 | WATER | REVIEW | Needs Review | |
| 05/21/2009 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 05/21/2009 | DAVE MANN | FIRE | REVIEW | Denied | Development plan indicates fire sprinklers are to be provided for this building. Please include the following fire sprinkler design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. 5. Show method of suppling water to sprinkler system. |