Review Details: POST 3RD PARTY REVIEW

Permit Number - T09CM01047
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2009 CPIERCE1 WATER REVIEW Needs Review
05/21/2009 CPIERCE1 ZONING REVIEW Needs Review
05/21/2009 DAVE MANN FIRE REVIEW Denied Development plan indicates fire sprinklers are to be provided for this building. Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
5. Show method of suppling water to sprinkler system.