Permit Number: T09CM01045
Parcel: 128102940

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01045
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2009 STEVE SHIELDS ZONING REVIEW Approved
04/28/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/29/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/29/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Exhaust fan EF-1 appears to be installed in an area having a return air plenum; positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006.
04/29/2009 JWILLIA5 BUILDING-COMMERCIAL REVIEW Approved
04/29/2009 ROBERT SHERRY WATER REVIEW Approved
04/29/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/29/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
04/29/2009 JWILLIA5 ZONING HC SITE REVIEW Approved
04/29/2009 JWILLIA5 ADA REVIEW Passed
04/30/2009 MARTIN BROWN FIRE REVIEW Approved
05/13/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2009 DELMA ROBEY OUT TO CUSTOMER Completed