Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01045
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/28/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 04/29/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/29/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Exhaust fan EF-1 appears to be installed in an area having a return air plenum; positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006. |
| 04/29/2009 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/29/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/29/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/29/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 04/29/2009 | JWILLIA5 | ZONING HC SITE | REVIEW | Approved | |
| 04/29/2009 | JWILLIA5 | ADA | REVIEW | Passed | |
| 04/30/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/13/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/13/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |