Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM01041
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/20/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. REVISIONS PAGE 10: SHEET A5.4 WAS NOT INCLUDED IN THIS REVIEW SET. PROVIDE. |
| 05/27/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the HVAC arrangement for the Pharmacy restroom (detail 6/M2); it appears to have a supply diffuser and a return grille, but no exhaust fan. Explain how this complies with the requirements of Sections 403.2.1, 403.3.3, and 918.6, IMC 2006. |
| 06/01/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The plan revision letter states that since the existing Snack Bar is to remain, all of the plumbing work shown on sheet P2.2 is to be deleted from the scope of work. Indicate this on the drawing to eliminate confusion in the field. 2. Provide listing information for the proposed automatic grease separator, RD023 and its associated pump. |
| 06/08/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/16/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/18/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 06/18/2010 | SUE REEVES | REJECT SHELF | Completed |