Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01028
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/29/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/08/2009 | RMYERS1 | WATER | REVIEW | Approved | |
| 05/08/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/14/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/22/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 3894 N oracle Rd.---T09CM01028 TI Restaurant, Pizza Hut The electrical plans have been denied for the following items, address each individually and indicate how each was addressed. 1. Panels A and B which will be replaced appear to have a table in front and below them, indicate on plan that there will be clearance for them as required by NEC 2005, 110.26, or relocate. 2. Provide information regarding panel note S on the shunt trip breaker to be controlled by the fire extingushing system,how will this be accomplished. 3. State on plan what the AIC ratings will have to be for the panels. Ray T Majuta DSD City of Tucson Elect Plan Ck 5/24/09 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/01/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 06/01/2009 | SUE REEVES | REJECT SHELF | Completed |