04/28/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 5855 E Speedway Bl
T09CM01025
Retail T I Verizon


The electrical plans have been denied for the following items:
1. Commercial submittal requirements for City Of Tucson DSD state that the total load (amperage) be indicated on the plan as well as the new tenant load. Plan shows only tenant load.
2. Sheet E-3, one line diagram shows Pnl PL1 fed from Transformer LP1 and that Pnls LP2 and LP3 are fed from Transformer LP2,3. The Pnl schedule for Pnl LP1 shows Pnl LP2 on it.


Ray T Majuta
DSD City of Tucson
Electrical Plan Check
520-837-4988
4/27/09