Permit Number: T09CM00965
Parcel: 13342001G

Address:
1925 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00965
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2009 DAVE MANN FIRE REVIEW Needs Review
04/24/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/28/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET AB1 OF 4; GENERAL NOTES (1): ADD ..."AS INDICATED ON SHEETS AB2, AB3, AND AB4"...
2. SEE BUILDING COMMENTS FOR PROJECT T09CM00963.
04/29/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
05/05/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: May 5, 2009
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM00965 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T09CM00965). Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan (D09-0009). Please submit two copies of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan (D09-0009). Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
05/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments for T09CM00963, these items required to be corrected since plans are same for Canopy and Dispensers as for Convenience Store.
Ray T Majuta
Electrical Plan Ck
5-08-09
05/13/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Quick Trip #1493
T09CM00963, T09CM00965 & T09BU00600
Building Plan (1st Review)

TRANSMITTAL DATE: May 13, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm00963.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
05/21/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Passed
05/21/2009 ROBERT SHERRY WATER REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2009 DELMA ROBEY OUT TO CUSTOMER Completed
09/25/2009 SUE REEVES REJECT SHELF Completed