Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM00951
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2009 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/22/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 04/22/2009 | LHANLY1 | FIRE | REVIEW | Passed | |
| 04/24/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/24/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |