Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM00934
Parcel: 131060090

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM00934
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: Pita King Express
T09CM00934
T I Restaurant


Electrical plans have been denied for the following items:


1.Sheet E-2 circuit marked P-24,26 should be marked P-36,38.
2. Sheet E-2 circuit K-37,29,41, should be marked P-37,39,41
3. Cannot locate cir's P-17,19 or 23, they show loads in panel.
4. Sheet E-2, circuit P,12 is used once in office as a receptacle and is also used in the lighting circuit.



Ray T Majuta
DSD City of Tucson
Elect Plan CK
520-837-4988
4/24/09

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2009 CPIERCE1 OUT TO CUSTOMER Completed