Permit Number: T09CM00932
Parcel: 10512024E

Address:
4040 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM00932
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2009 MARTIN BROWN FIRE REVIEW Approved
04/22/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. STRUCTURAL CALCULATIONS; DRAWINGS: THE DETAIL SHOWN IN THE CALCULATIONS MUST BE ON THE SET OF FULL SIZED DRAWINGS (KEY NOTE 5 ON SHEET SL2.0 INDICATES REFERENCE TO STRUCTURAL DRAWING FOR POLE BASE CONSTRUCTION).
2. GENERAL: ADD STRUCTURAL GENERAL NOTES TO THE FULL SIZED DRAWING.
3. STRUCTURAL CALCULATIONS; PAGE 2: LIST THE SOURCE FOR SOIL VALUES USED IN THIS DESIGN (SOIL REPORT NUMBER, ETC.).
05/04/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
05/19/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 4040 N Oracle RD, T09CM00932
Target Site Lighting

Elexctrical denied for the following:
1. Provide a panel schedule indicating the existing loads on the panels plus new loads.
2. Show location of panels.



Ray T Majuta
City of Tucson
Electrical Plan Check
5/20/09
520-837-4988

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2009 DELMA ROBEY OUT TO CUSTOMER Completed
05/27/2009 SUE REEVES REJECT SHELF Completed