Permit Number: T09CM00846
Parcel: 117200250

Address:
265 S CHURCH AV

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T09CM00846
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2009 STEVE SHIELDS ZONING REVIEW Approved
04/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/16/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project:265 S Church,Temporary Power for remedial extraction,

Denied for the following.
1. The site plan shows a City of Tucson owned transformer, the electrical sheet shows power transformer by TEP-b utility.
Estabilish owner.
2. If City of Tucson owner provide information on transformer showing method of tie in to transformer, availabity of terminals, load avalibility,
RT Majuta
Elect Plans Ex
DSD City of Tucson
4-16-09
04/16/2009 ROBERT SHERRY WATER REVIEW Passed
04/16/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/16/2009 ANY WWM REVIEW Active
04/16/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/16/2009 PAUL MACHADO ENGINEERING REVIEW Approved
04/16/2009 DAVE MANN FIRE REVIEW Approved
04/16/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
04/16/2009 RONALD BROWN ADA REVIEW Passed
04/24/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed