Review Details: REVISION - - 3RD
Permit Number - T09CM00841
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/14/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations for AC-6, using the combined outdoor air rate for the space (Table 6-1, ASHRAE 62.1-2004) and an air distribution effectiveness (Table 6-2) of 0.8. The calculations for AC-7 and AC-8 are similarly incorrect but the total supply of outside air is adequate. |