Permit Number: T09CM00841
Parcel: 13606002C

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T09CM00841
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2009 GERRY KOZIOL WWM REVIEW Approved
10/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations for AC-6, using the combined outdoor air rate for the space (Table 6-1, ASHRAE 62.1-2004) and an air distribution effectiveness (Table 6-2) of 0.8. The calculations for AC-7 and AC-8 are similarly incorrect but the total supply of outside air is adequate.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2009 CINDY AGUILAR APPROVAL SHELF Completed
10/15/2009 CINDY AGUILAR OUT TO CUSTOMER Completed