Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2009 RONALD BROWN ZONING HC REVIEW Approved
10/08/2009 MRAMBER1 WATER REVIEW Approved
10/08/2009 MATTHEW RAMBER PLUMBING-COMMERCIAL REVIEW Approved
10/08/2009 MATTHEW RAMBER MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations for AC-6, using the combined outdoor air rate for the space (Table 6-1, ASHRAE 62.1-2004) and an air distribution effectiveness (Table 6-2) of 0.8. The calculations for AC-7 and AC-8 are similarly incorrect but the total supply of outside air is adequate.
10/08/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/08/2009 DROBEY1 WWM REVIEW Needs Review