Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00813
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/24/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: 3/32" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING. 2. SHEET A.1; KEYNOTES: COULD NOT LOCATE KEYNOTE 2 ON PLAN. VERIFY. 3. CALCULATIONS SHEET 16; SHEET S.2 (DETAIL 9): CALCULATIONS CALL FOR 1/2" DIAMETER X 8" LAG SCREWS WHILE THE DETAIL DENOTES 1/2" DIAMETER X 6" LAG SCREWS. CLARIFY. |
| 04/28/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 05/01/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/04/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 05/04/2009 | SUE REEVES | REJECT SHELF | Completed |