Permit Number: T09CM00813
Parcel: 126122680

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00813
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2009 DAVE MANN FIRE REVIEW Approved
04/24/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: 3/32" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING.
2. SHEET A.1; KEYNOTES: COULD NOT LOCATE KEYNOTE 2 ON PLAN. VERIFY.
3. CALCULATIONS SHEET 16; SHEET S.2 (DETAIL 9): CALCULATIONS CALL FOR 1/2" DIAMETER X 8" LAG SCREWS WHILE THE DETAIL DENOTES 1/2" DIAMETER X 6" LAG SCREWS. CLARIFY.
04/28/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
05/01/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2009 CPIERCE1 OUT TO CUSTOMER Completed
05/04/2009 SUE REEVES REJECT SHELF Completed