Permit Number: T09CM00804
Parcel: 141114100

Address:
7850 S RITA RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T09CM00804
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE VERTICAL AND LATERAL CALCULATIONS BY THE ENGINEER OF RECORD FOR THE SHELTER. INDICATE ON THE DRAWINGS THE REQUIRED FOUNDATION (PER IBC SECTION 18 AND CITY OF TUCSON AMENDMENTS), AND HOW THE BUILDING IS TIED TO THE FOUNDATION TO RESIST LATERAL SLIDING AND UPLIFT LOADS.
2. INDICATE ALL DESIGN LOADS AND DESIGN INFORMATION ON THE DRAWINGS PER THE IBC SECTION 1603.
07/31/2009 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
08/03/2009 STEVE SHIELDS ZONING REVIEW Approved
08/07/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:7850 E Rita Rd
New Cell Site
T09CM00804

The electrical plans have been denied for the following:

1. Provide a fault current analysis for the service and panel.
2. The one line diagram is incorrect, the meter goes ahead of the main overcurrent device.
3. Provide a panel schedule showing voltage,amperage,phase,individual load and sum load.
4. The one line shows Panel Lp-1 feeding the power cabinet with a conduit with 6 # 2's and 1#2 neutral , how will these be connected to panel ? May require derating depending on the circuit breaker sizes.
5. Show circuits for receptacles,light,and Ac as shown on other sheets, also no switch noted for light in new room.
6. Show layout of equipment in new shelter.

Ray T Majuta
Electrical Plan Check
PSDS City of Tucson
8/7/09
Ray,Majuta@tucsonaz.gov
08/12/2009 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Needs Review waiting for responce from communications

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2009 SUE REEVES OUT TO CUSTOMER Completed
08/31/2009 SUE REEVES REJECT SHELF Completed