Permit Number: T09CM00797
Parcel: 132191120

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00797
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2009 GERRY KOZIOL WWM REVIEW Approved
08/03/2009 JASON GREEN ENGINEERING REVIEW Approved
08/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/06/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show that the floor of the restroom slopes toward the floor drain. Reference 411.4 2006 UPC: Floors shall be sloped to the floor drains. 2. The flow control device for the hydromechanical grease interceptor not installed per code. Reference 1014.2.1 2006 UPC: Each plumbing fixture or piece of equipment connected to a hydromecanical grease interceptor shall be provided with an approved type of vented flow control installed in a readily accessible and visible location.
08/11/2009 TERRY STEVENS ZONING REVIEW Approved