Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM00797
Parcel: 132191120

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00797
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2009 MARTIN BROWN FIRE REVIEW Approved
04/08/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; West District; 5,104 Square Feet Retail Building; $28,167.95
04/09/2009 GERRY KOZIOL WWM REVIEW Denied quiktrip (D08-0051) issued with grease interceptor
need PCRWRD 3RD Floor review & approval- fronts 15" public sewer- Karen Sanson/ Roy Montoya 740-5369
04/10/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: April 10, 2009
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM00797 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T09CM00797) for the above referenced property. Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan (D08-0051). Please submit two copies of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan. Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
04/13/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A6.1; DETAIL A4: REFERENCE TO DETAIL G6-A6.1 SHOULD BE G4? VERIFY.
2. SHEET S1.1; CALCULATIONS SHEET 3: THE CONCRETE BASIS FOR DESIGN IN THE CALCULATIONS IS 3000 PSI FOR SLABS AND FOUNDATIONS, WHILE THE GENERAL NOTES IN THE DRAWINGS INDICATE A CONCRETE COMPRESSIVE STRENGTH OF 4000 PSI. CLARIFY.
3. SHEET S1.1; CALCULATIONS SHEET 3: THE BOLTS BASIS FOR DESIGN IN THE CALCULATIONS IS A307. ADD A HIGH STRENGTH BOLT SPECIFICATION TO THE CALCULATIONS TO MATCH THE GENERAL NOTE FOR BEAM AND COLUMN CONNECTIONS.
4. SHEET S1.1; CALCULATIONS SHEET 3: THE REINFORCEMENT BASIS FOR DESIGN IN THE CALCULATIONS IS 60 KSI FOR #6 AND LARGER, AND 40 KSI FOR #5 AND SMALLER, WHILE THE GENERAL NOTES IN THE DRAWINGS INDICATE GRADE 60 FOR ALL BARS. CLARIFY.
5. SHEET S2.1; CALCULATION SHEETS F1 AND F6: THE WALL REFERENCED AS W4 IN THE CALCULATIONS DOES NOT MATCH THE FOUNDATION PLAN. CALL OUT THE WALL REINFORCING AND FOOTING SIZE ON THE PLAN TO MATCH THE CALCULATIONS (8" BLOCK WITH #5 AT 16" OC AND 3'-3" WIDE X 12" FOOTING WITH 4-#5). VERIFY.
6. SHEET S2.1; SECTION M1/M1A: REVISE THE NOTE UNDER THE FOOTING TO READ '2'-0" AT M1A' TO MATCH PLAN. VERIFY.
7. SHEET S3.1; ROOF FRAMING PLAN: LOCATE THE COLUMNS FOR THE MECHANICAL SCREEN IN THE EAST/WEST DIRECTION.
8. SHEET S5.1 (DETAIL LP1); SHEET E0.1 (DETAIL N12): THE ELECTRICAL SHEET SHOULD REFERENCE STRUCTURAL FOR THE LIGHT POLE FOOTING.
9. SHEET S4.1 (DETAIL K9); CALCULATIONS: DID NOT FIND A CALCULATION FOR THE TRASH ENCLOSURE WALL AND FOOTING. CLARIFY.
04/14/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
04/15/2009 TERRY STEVENS ZONING REVIEW Denied 04/15/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
04/16/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/20/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the floor of the restroom slopes toward the floor drain. Reference: Section 411.2, UPC 2006.
2. Clarify how the CW shut off valve for the building is accessible at all times. Reference: Section 605.2, UPC 2006.
3. Clarify how the flow control device for the hydromechanical grease interceptor is readily accessible and complies with the installation requirements of the manufacturer. Reference: Sections 310.4 and 1014.2.1, UPC 2006.
4. Clarify how a direct connection of the creamer machine drains to the indirect waste manifold (Detail M12/P2.1) complies with the requirements of Section 801.2.3, UPC 2006.
04/20/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/20/2009 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2009 CPIERCE1 OUT TO CUSTOMER Completed
04/21/2009 SUE REEVES REJECT SHELF Completed