Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T09CM00796
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/09/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Passed | COT PROJECT MUST USE ADAAG |
| 04/09/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. These drawings very closely represent City of Tucson Comfort Station Model No. T08-M0016. However, reference to that effect can not be found anywhere on the drawings. 2. Please provide structural calculations for the new building. 3. Provide structural calculations for the irrigation antenna foundation pole. |
| 04/09/2009 | RONALD BROWN | ADA | REVIEW | Denied | 1. The urinal shown must be accessible as per ADAAG Section 4.23.5 and 4.18. A urnial enclosed in a 4'-10" x 2'-10" toilet stall with a door is not accessible, due to lack of turn around space. As per model T08-M0016, Alternate Open Screen Plan, the urinal was replaced with a standard toilet stall. |
| 04/16/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/21/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/29/2009 | RMYERS1 | WATER | REVIEW | Passed | |
| 04/29/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 04/29/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | plumbing systems with quick closing valves require hammer arrestors. 609.10 2006 upc. 2. verify water pressure at reclaimed water meter. see 608.2 2006 upc. 3. p1.0 detail five check arrowed description to verify no cross connection btween reclaimed and potable water systems. plan shows one inch domestic cold water to water closet. |
| 04/30/2009 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/11/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |