Permit Number: T09CM00782
Parcel: 117020340

Address:
1044 N 3RD AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T09CM00782
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2009 GERRY KOZIOL WWM REVIEW Denied PROPERTY DOES NOT FRONT PUBLIC SEWER- NEED PCRWRD REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER. ILENE DECKARD 3RD FLOOR 740-6544
04/17/2009 MICHAEL ST. PAUL ZONING REVIEW Denied Historic review required. Contact Frank Podgorski @ 837-4962.
05/04/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-05-09
Activity: T09CM00782
Address: 1044 N. 3rd Ave.
Applicant: Maritza Dicenso

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FLOOR PLANS:
3. Provide sufficient emergency escape/rescue openings from sleeping rooms, R310. Minimum net opening of 5.7square feet for floors above grade level, 5 square feet for floors at grade level. Maximum sill height = 44". Minimum clear opening = 24" high x 20" wide.

PLUMBING PLAN:
4. Provide the maximum developed length of water line from the meter the furthest appliance served and the size of the water meter, UPC Table 6-6. Size the water supply line according to the proposed demand.
5. Specify fiber-cement board backing in tub/shower enclosures, R702.4.2.
6. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10.

MECHANICAL PLAN:
7. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1.

ELECTRICAL PLAN:
8. Show locations of smoke detectors (every sleeping room and hallways leading to). All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R313. Ref: hallway leading to bedroom #2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2009 CPIERCE1 OUT TO CUSTOMER Completed
05/11/2009 SUE REEVES REJECT SHELF Completed