Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T09CM00782
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/09/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | PROPERTY DOES NOT FRONT PUBLIC SEWER- NEED PCRWRD REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER. ILENE DECKARD 3RD FLOOR 740-6544 |
04/17/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Historic review required. Contact Frank Podgorski @ 837-4962. |
05/04/2009 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Date: 5-05-09 Activity: T09CM00782 Address: 1044 N. 3rd Ave. Applicant: Maritza Dicenso Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: 1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. 2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. FLOOR PLANS: 3. Provide sufficient emergency escape/rescue openings from sleeping rooms, R310. Minimum net opening of 5.7square feet for floors above grade level, 5 square feet for floors at grade level. Maximum sill height = 44". Minimum clear opening = 24" high x 20" wide. PLUMBING PLAN: 4. Provide the maximum developed length of water line from the meter the furthest appliance served and the size of the water meter, UPC Table 6-6. Size the water supply line according to the proposed demand. 5. Specify fiber-cement board backing in tub/shower enclosures, R702.4.2. 6. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10. MECHANICAL PLAN: 7. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1. ELECTRICAL PLAN: 8. Show locations of smoke detectors (every sleeping room and hallways leading to). All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R313. Ref: hallway leading to bedroom #2. If you have any questions please contact: Clayton Trevillyan 520.837.4913 Residential Plan Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/11/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
05/11/2009 | SUE REEVES | REJECT SHELF | Completed |