05/15/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-18-09
Activity: T09CM00764 2nd review
Address: 1307 W. St. Clair #2
Applicant: Steve Gostro

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

STRUCTURAL PLANS:
2. Justify roof ventilation calculation, R806.2 (1 square foot of ventilation is required for every 150 square feet of roof area). Ventilation specified does not match calculation provided.

It is unclear how the 24 vent openings specified, at 4" diameter each, is equal to 7.33 square feet. Please refer to R806.4 and determine if ventilation is necessary.

ELECTRICAL PLAN:
3. Specify one electrical drop (from utility) to property, SR 3.01.

Tucson Electric Power will only provide one drop to the property per SR-3.01. Show one electrical drop and modify the riser diagram accordingly to accommodate the distribution of power on site.