Permit Number: T09CM00764
Parcel: 116122070

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T09CM00764
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2009 GERRY KOZIOL WWM REVIEW Approved
05/05/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-06-09
Activity: T09CM00764
Address: 1307 W. St. Clair #2
Applicant: Steve Gostro

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Provide gas piping for structure or submit exemption documentation, Arizona Statute 30-809.

INCLUSIVE HOME DESIGN:
3. Provide Inclusive Home Design notes on plan.

FLOOR PLANS:
4. Specify fiber-cement board backing in tub/shower enclosures, R702.4.2.
5. Specify all door sizes on plan in accordance with the City of Tucson Inclusive Home Design ordinance.
6. Verify location of window in living room (floor plan and elevation drawings disagree and braced wall panel indicated requires at least 48").

STRUCTURAL PLANS:
7. Justify roof ventilation calculation, R806.2 (1 square foot of ventilation is required for every 150 square feet of roof area). Ventilation specified does not match calculation provided.

ELEVATIONS:
8. Specify the pitch of the roof slope, R905.

SECTIONS - DETAILS:
9. Clarify anchor bolt spacing (sheet 2 does not agree with sheet 4).

PLUMBING PLAN:
10. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater.
11. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10.
12. Specify a dedicated water meter for the new residence, IPC 301.4.1.
13. Provide vent piping through the roof so that the aggregate cross-sectional area shall not be less than that of the largest required building sewer, UPC 904.1.

ELECTRICAL PLAN:
14. Provide an accurate electrical load calculation, E3502.2.
15. Specify one electrical drop (from utility) to property, SR 3.01.
16. At least one wall switch controlled light or outlet must be provided at outdoor entrances or exits, E3803.3.
17. Bedroom outlets shall be protected with combination-type arc-fault breakers (including smoke detectors), E3802.12.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
05/06/2009 JEFF DRUMM LANDFILL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2009 DELMA ROBEY OUT TO CUSTOMER Completed