Permit Number: T09CM00748
Parcel: 12112056C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00748
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2009 DAVE MANN FIRE REVIEW Approved
04/03/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/03/2009 SREEVES1 ADA REVIEW Passed
04/08/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET AB1 OF 2 (FOOTING NOTES); GEOTECHNICAL REPORT 08-0834: FOOTING NOTE 2 DOES NOT COMPLY WITH THE RECOMMENDATIONS OF THE GEOTECHNICAL REPORT. REVISE NOTES AND CALCULATIONS AS REQUIRED.
2. SHEET AB2 OF 2; FOOTING DETAILS: REVISE DETAILS AS REQUIRED TO COMPLY WITH THE RECOMMENDATIONS OF THE GEOTECHNICAL REPORT (PER PLAN NOTE ON SHEET AB2).
04/10/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
04/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The minimum opening height for a scupper is 4". Reference: Section 1101.11.2.1, UPC 2006.
04/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments for T09CM00747,


Ray T Majuta
DSD City of Tucson
4-13-09
04/21/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: May 4, 2009
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM00748 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T09CM00747). Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan (D09-0006). Please submit two copies of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan (D09-0006). Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
04/21/2009 CPIERCE1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2009 CPIERCE1 OUT TO CUSTOMER Completed