Permit Number: T09CM00747
Parcel: 12112056C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00747
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2009 DAVE MANN FIRE REVIEW Approved Separate, deferred submittal required for underground fuel tanks.
04/03/2009 GERRY KOZIOL WWM REVIEW Approved
04/03/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
04/08/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET N1.1; SUMMARY OF PROJECT: COMPLETE THE LOCATION OF THE PROJECT.
2. SHEET S1.1; CALCULATIONS SHEET 3: THE CONCRETE BASIS FOR DESIGN IN THE CALCULATIONS IS 3000 PSI FOR SLABS AND FOUNDATIONS, WHILE THE GENERAL NOTES IN THE DRAWINGS INDICATE THE CONCRETE COMPRESSIVE STRENGTH OF 4000 PSI. CLARIFY.
3. SHEET S1.1; CALCULATIONS SHEET 3: THE BOLTS BASIS FOR DESIGN IN THE CALCULATIONS IS A307. ADD A HIGH STRENGTH BOLT SPECIFICATION TO THE CALCULATIONS TO MATCH THE GENERAL NOTE FOR BEAM AND COLUMN CONNECTIONS.
4. SHEET S1.1; CALCULATIONS SHEET 3: THE REINFORCEMENT BASIS FOR DESIGN IN THE CALCULATIONS IS 60 KSI FOR #6 AND LARGER, AND 40 KSI FOR #5 AND SMALLER, WHILE THE GENERAL NOTES IN THE DRAWINGS INDICATE GRADE 60 FOR ALL BARS. CLARIFY.
5. SHEET S3.1; ROOF FRAMING PLAN: LOCATE THE COLUMNS FOR THE MECHANICAL SCREEN IN THE EAST/WEST DIRECTION.
6. SHEET S5.1 (DETAIL LP1); SHEET E0.1 (DETAIL N12): THE ELECTRICAL SHEET SHOULD REFERENCE STRUCTURAL FOR THE LIGHT POLE FOOTING.
7. SHEET S4.1 (DETAIL K9); CALCULATIONS: DID NOT FIND A CALCULATION FOR THE TRASH ENCLOSURE WALL AND FOOTING. CLARIFY.
04/09/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
04/13/2009 ROBERT SHERRY WATER REVIEW Approved
04/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the floor of the restroom slopes toward the floor drain. Reference: Section 411.2, UPC 2006.
2. Clarify how the CW shut off valve for the building is accessible at all times. Reference: Section 605.2, UPC 2006.
3. Clarify how the flow control device for the hydromechanical grease interceptor is readily accessible and complies with the installation requirements of the manufacturer. Reference: Sections 310.4 and 1014.2.1, UPC 2006.
4. Clarify how a direct connection of the creamer machine drains to the indirect waste manifold (Detail M12/P2.1) complies with the requirements of Section 801.2.3, UPC 2006.
04/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 5151 E Speedway, T09CM00747, Store
T09CM00748, Canopy

Electrical plans denied for the following,

1.Sheet E1.1 shows a 1000 amp circuit breaker for main at DB-T, and no feeders called out. Sheet E2.3 on one line shows 2 4" conduits with 4 #500 kcmil conductors which equals 760 amps.The load shown is 770 Amps.
2. Sheet E2.3 also shows an 800 amp circuit breaker main. different from Sheet E1.1.
3.Size the ground for the main service on sheet E2.3.
4. Provide information sheet on Veeder Root System.
5. Cannot locate following circuits on Power Plan sheet however they are on the Panel Schedule, Panel E 16,18,22,24,28,30,34,36.


Ray T Majuta
DSD City of Tucson,Az
Electrical Plan Ck
520-837-4988
4-13-09
04/21/2009 SREEVES1 ZONING REVIEW Needs Review
04/21/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: May 4, 2009
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM00747 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T09CM00747). Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan (D09-0006). Please submit two copies of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan (D09-0006). Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2009 CPIERCE1 OUT TO CUSTOMER Completed