Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00745
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/02/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 04/02/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. |
| 04/03/2009 | RONALD BROWN | ADA | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 04/03/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/03/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PER IBC SECTION 2902.4, THE ACCESSIBLE ROUTE TO PUBLIC FACILITIES SHALL NOT PASS THROUGH STORAGE ROOMS (WAREHOUSE). IS THIS RESTROOM FOR PUBLIC USE, OR IS IT FOR EMPLOYEES ONLY? ARE THERE PUBLIC GANG TOILETS WITHIN THIS COMPLEX. 2. PER TABLE 2902.1 OF THE IBC, A DRINKING FOUNTAIN AND SERVICE SINK ARE BOTH REQUIRED. 3. PLAN KEY NOTE 6 ON A1 NEEDS TO PROVIDE CONNECTION SIZE/SPACING/QUANTITY TO THE TOP OF THE STUD AND TO THE EXISTING STRUCTURE. |
| 04/03/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/03/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the minimum plumbing fixtures for mercantile occupancy. |
| 04/14/2009 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 04/14/2009 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 04/14/2009 | CAGUILA1 | ZONING HC SITE | REVIEW | Needs Review |