Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM00745
Parcel: 137055300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00745
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
04/02/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006.
04/03/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/03/2009 ROBERT SHERRY WATER REVIEW Approved
04/03/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PER IBC SECTION 2902.4, THE ACCESSIBLE ROUTE TO PUBLIC FACILITIES SHALL NOT PASS THROUGH STORAGE ROOMS (WAREHOUSE). IS THIS RESTROOM FOR PUBLIC USE, OR IS IT FOR EMPLOYEES ONLY? ARE THERE PUBLIC GANG TOILETS WITHIN THIS COMPLEX.
2. PER TABLE 2902.1 OF THE IBC, A DRINKING FOUNTAIN AND SERVICE SINK ARE BOTH REQUIRED.
3. PLAN KEY NOTE 6 ON A1 NEEDS TO PROVIDE CONNECTION SIZE/SPACING/QUANTITY TO THE TOP OF THE STUD AND TO THE EXISTING STRUCTURE.
04/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the minimum plumbing fixtures for mercantile occupancy.
04/03/2009 RONALD BROWN ADA REVIEW Denied 1. SEE BUILDING COMMENTS.
04/14/2009 CAGUILA1 WWM REVIEW Needs Review
04/14/2009 CAGUILA1 FIRE REVIEW Needs Review
04/14/2009 CAGUILA1 ZONING HC SITE REVIEW Needs Review