Permit Number: T09CM00726
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00726
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM00726
5870 E Broadway Bl
TI Retail , Buckle

The Interior Lighting Budget calculations provided shows a square footage area of 4854 at 1.7 watts per sq ft. The front sheet on the plan shows a sq ft area of 4354, and the IECC 2006 table 505.5.2 allows 1.5 watts per sq ft. This figure would allow 6531 watts for the area . Please clarify.
2. The allowed amperage for the space has not been confirmed by Park Mall.

Ray Majuta
Elect Plans Ex
DSD City of Tucson
502-837-498
4-07-09
04/07/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Indirect waste receptors shall not be installed in a restroom. Hub drains are not an approved plumbing fixture. Reference: Sections 411.1 and 804.1, UPC 2006.
04/07/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved .