Permit Number: T09CM00726
Parcel: 12801005H

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM00726
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2009 LEERAY HANLY ZONING HC SITE REVIEW Approved
04/02/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 5870 E Broadway Bl
T09CM00726
TI Retail , BUCKLE

The electrical plans have been denied for the following ----
1. Provide the allotted amperage for the space by Mall Management, they should provide you with a total which you will add this space to , for a complete total.
2. Provide Interior Lighting Power Allowances per The 2006 IECC Section 505.



Ray T Majuta
DSD Elect Plan Ck
City of Tucson
520-837-4988
4-02-09
04/02/2009 DAVE MANN FIRE REVIEW Approved
04/03/2009 GERRY KOZIOL WWM REVIEW Approved
04/07/2009 DROBEY1 MECHANICAL-COMMERCIAL REVIEW Needs Review