Permit Number: T09CM00726
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00726
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2009 STEVE SHIELDS ZONING REVIEW Approved
04/01/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference: Section 606.1, IMC 2006.
3. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.3, IMC 2006.
4. The minimum insulation for ducts located outside of the building envelope or in a space that freely communicates with the outside is R-8. The minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2 (installed). Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
5. Provide calculations demonstrating adequate ventilation. Reference: Sections 403.3 and 403.3.2, IMC 2006
04/01/2009 THAUSER1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/01/2009 ROBERT SHERRY WATER REVIEW Approved
04/01/2009 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
04/01/2009 GERRY KOZIOL WWM REVIEW Needs Review
04/01/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/01/2009 JASON GREEN ENGINEERING REVIEW Approved
04/01/2009 THAUSER1 FIRE REVIEW Needs Review
04/01/2009 THAUSER1 ZONING HC SITE REVIEW Needs Review
04/01/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/01/2009 JWILLIA5 ADA REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2009 THAUSER1 OUT TO CUSTOMER Completed