Permit Number: T09CM00717
Parcel: 112052350

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING-WALKTHRU

Permit Number - T09CM00717
Review Name: RESIDENTIAL BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2009 TERRY STEVENS ZONING REVIEW Passed
03/31/2009 JASON GREEN ENGINEERING REVIEW Approved March 31, 2009
FLOODPLAIN USE PERMIT NO.: T09OT00635
ADDRESS: 2221 E La Madera Dr, Tucson Arizona 85719
PROPERTY OWNER: John Hurley
2221 E La Madera Dr, Tucson Arizona 85719


The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone AE per the Flood Insurance Rate Maps 04019C1639K, specifically described as:
A portion of Parcel 112-05-2350, SHAHEEN ESTATES LOT 11 BLK 5

For the purpose of installing a solar hot water heater and a Photovoltaic System to an existing non-conforming structure.


In reviewing this Floodplain Use Permit application for improvements to an existing floodprone structure, it has been concluded that the cumulative value of proposed improvements to this structure for both these activities, as supported by documentation provided by the applicant, is less than 50% of the current value of the existing structure.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard Area Regulations, and is bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require application for, review and approval of an additional Floodplain Use Permit.

This floodplain use permit is issued with the following 12 conditions:

1) All improvements proposed under this permit will be cumulative in percentage, to include this project.
2) The proposed improvements shall not impose conditions that would increase the flood damage potential to the combined proposed and existing building, by 50 percent or greater of the existing structure's value.
3) A cost estimate was provided showing that the improvements are less than 50 % (estimate was 33.4%) of the assessed value ($125,148), as shown on the Pima County Assessors Website. No person shall repair or alter property in a piecemeal manner so as to avoid the provisions of Section 26-4.1.a.3, Chapter 26-Tucson Code. The estimate will be recorded and if piecemeal permits for this construction are applied for the cost estimate will be added to it.
4) This project is located in a portion of the FEMA Special Flood Hazard Area Zone AE per the Flood Insurance Rate Maps 04019C1639K.
5) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
6) This Floodplain Use Permit is issued concurrently with the improvement plans/permit. Copies of these documents shall be kept in a readily accessible location on site at all times.
7) Any future permanent, freestanding walls or other structures shall have separate floodplain use permit applications submitted to this office for review and approval.
8) An application/processing fee of $50.00 (submittal fee) must accompany each future request for work to be authorized under this floodplain use permit. Engineering study review fees of $150.00 may be imposed based upon the fee schedule in the current floodplain ordinance.
9) The associated improvements are with permit activity numbers T09CM00716 and T09CM00717.
10) The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be done to the existing building, and that all additions, improvements or repairs to the building are included in the construction plans and/or documents herewith. No other improvements, repairs, reconstruction, additions or remodeling have been made to the structure that is not indicated in the attached plans and/or documents.
11) Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Division. This permit may be renewed for up to one year at the sole discretion of the City Engineer or designated representatives.
12) This permit is specific to the improvements for 2221 E La Madera Dr as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: The Solar Store
ADDRESS: 2833 N Country Club Blvd, Tucson, AZ 85716
PHONE: 520-322-5180
CONTRACTOR: The Solar Store
ADDRESS: 2833 N Country Club Blvd, Tucson, AZ 85716
PHONE: 520-322-5180

(EXPIRATION DATE) Month: 03 Day: 31 Year: 2010

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
03/31/2009 TERRY STEVENS NPPO REVIEW Passed
04/02/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM00717
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.
CALCULATIONS
1. Maximum Photovoltaic System Voltage (Voc x 1.13) NEC 690.7 and Table 690.7. Show an inverter with appropriate specifications for this calculation.
2. DC Overcurrent Protective Device and Conductor Sizing for Photovoltaic Source Circuits and Module Interconnection Conductors (Isc x 1.25 x 1.25) Reference NEC 690.8 (A) (1) and (B) (1). Show a complete calculation for determining conductor requirements.
3. Maximum conductor ampacity is determined by applying correction and adjustment factors for temperature of insulation rating of 90C and CCC proximity (I x 0.82 x .8 {if 4-6}) Reference NEC 310.15. The adjusted conductor rating may not be less than the calculated Conductor Sizing.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review