Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM00704
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2009 | DAVE MANN | FIRE | REVIEW | Denied | Exit E113B cannot exit through the stock room unless IFC 1014 Exc. 2.4 is complied with. An alarm system is required IFC 907.2.7. |
| 03/31/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 04/03/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: 3/32" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR APPROVAL. 2. SHEET A1; NEW INTERIOR, NON-BEARING PARTITIONS: ALL NEW INTERIOR PARTITIONS MUST BE CAPABLE OF RESISTING LATERAL LOADS PER IBC SECTION 1607.13. INDICATE BY NOTE OR DETAIL THE CONNECTION (SIZE, SPACING) OF THE BASE TO THE EXISTING FLOOR SLAB, AND THE BRACING AT THE TOP OF THE PARTITION WALL (BRACE SIZE, SPACING, CONNECTION TO THE TOP OF THE PARTITION AND THE CONNECTION TO THE EXISTING STRUCTURE). 3. SHEET A7; DETAIL 1: ADD A VERTICAL GRAB BAR PER FIGURE 604.5.1 OF THE ICC/ANSI A117.1-2003. 4. SHEET S1; FRAMING PLAN 3: NO STRUCTURAL CALCULATIONS WERE PROVIDED FOR THE DOCK CANOPY. 5. SHEET S1; EXISTING ROOF AT NEW RTU #1, #2, AND #3: PROVIDE STRUCTURAL CALCULATIONS AND DETAILS AS REQUIRED FOR THE ADEQUACY OF THE EXISTING ROOF STRUCTURE UNDER THE NEW RTU LOADS. 6. SHEET S1; NEW LINTEL AT THE DOCK CANOPY: NO STRUCTURAL CALCULATIONS WERE PROVIDED. 7. SHEET S1/S2; NOTE ON GENERAL CONTRACTOR VERIFICATION OF EXISTING CONDITIONS: ANY NEW WORK RESULTING FROM THE GENERAL CONTRACTOR DOCUMENTATION SHALL BE CONSIDERED AS A REVISION TO THE PERMIT DOCUMENTS, AND WILL BE PROCESSED AS SUCH. |
| 04/14/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED WASTEWATER 5TH FLOOR CREDIT EVALUATION 520-740-6602 |
| 04/15/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 7125 E Broadway Bl Hobbylobby TI T09CM00704 Eleectrical Plans have been denied for the following: 1. The electrical plans provide insufficient information in order to review the project. Attached to the application you will find The City of Tucson Commercial Submittal Requirements. The last section oulines Electrical, some of these items you have, quite a few are missing. Review and submit the missing requirements for re-evaluation. Ray T Majuta Electrical Plan Check DSD City of Tucson 520-837-4988 4-15-09 |
| 04/28/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006. 2. Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reference: City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control. |
| 04/28/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping. Reference: Sections 103.2.3 and 1217.0, UPC 2006. 3. Clarify the location of the water heater serving the restrooms; is it floor-mounted or supported from the building structure. If it is not floor-mounted, provide information to show how the proposed water heater is to be supported from the building structure. Reference: Section 314.5, UPC 2006. 4. Show that the floors in the restrooms slope toward the floor drains. Reference: Section 411.2, UPC 2006. 5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 6. Show how the new water, waste and vent piping relates to the existing water supply and waste and vent systems and show that the additional connections do not cause the existing piping to be overloaded. Reference: Section 101.5.1, UPC 2006. 7. Provide information to show that the termination of a temperature and pressure relief from a water heater over the specified floor drain will not cause splashing or flooding. Reference: Sections 608.5 and 804.1, UPC 2006. 8. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. 9. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. |
| 04/28/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006 2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 3. Provide the installed weight of the rooftop equipment. Reference: Section 106.3.1, IMC 2006. 4. Provide balancing data for the exhaust fan for room 108. Reference: Section 106.3.1, IMC 2006. 5. Show the size, routing, and termination of the condensate drains from the new rooftop units. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 6. Provide the heating capacity and the electrical operating information for the new rooftop units. Reference: Section 301.6, IMC 2006 7. Provide sufficient heat for the new stock room to maintain a minimum temperature of 68 F on a design heating day (32 F). Reference: Section 309.1, IMC 2006. 8. Provide calculations demonstrating adequate ventilation. Reference: Section 403.1, IMC 2006. 9. Provide balancing data for the restroom exhaust fan. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference: Section 106.3.1 and Table 403.3, IMC 2006. 10. Complete recirculation of ventilation air from toilet rooms is prohibited. Controlling the exhaust fan with the room lights will result in complete recirculation whenever the lights are off. Reference: Section 403.2.1 (3), IMC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/01/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 05/01/2009 | SUE REEVES | REJECT SHELF | Completed |