Permit Number: T09CM00696
Parcel: 13711429H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM00696
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/01/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved DATE: June 1, 2009
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T09CM00696 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T09CM00692). Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan (D08-0044). Please submit two copies of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan (D08-0044). Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Bianca Ramirez, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
06/02/2009 STEVE SHIELDS ZONING REVIEW Approved
06/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Provide roof drainage calculations, showing the size and slope of the gutters and the slope of the horizontal roof leaders on the plans. Provide overflow protection for the roof. Reference: Section 1106.0, UPC 2006
06/10/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review Project: Hanson's To Go
1715 W Irvington RD
T09CM00696


The Electrical Plans have been denied for the following;

Comments dated 4-13-09 on Electrical requested the following,
1. a fixture cut of the type to be used on the canopy, which is provided on sheet S1.3.
2. Circuitry for fixtures, what circuits are the fixtures to be connected , however the panel and circuit numbers are provided.
3. Seals required for conduits going into hazardous area.

Please provide the on the electrical plans.



Ray T Majuta
Elect Plan Ck
City of Tucson DSD
6/09/09