Permit Number: T09CM00696
Parcel: 13711429H

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00696
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2009 DAVE MANN FIRE REVIEW Approved
03/30/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Hanson's Good to Go
T09CM00692 & T09CM00696
Building Plan (1st Review)

TRANSMITTAL DATE: March 30, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm00692.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
03/30/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 3/32" LETTERING IS REQUIRED ON ALL DRAWINGS.
2. SHEET CS: NOTE TO NOT SUBMIT THE COVERSHEET WITH THE DRAWINGS FOR PERMITTING. CLARIFY. SOME OF THIS INFORMATION SHOULD BE INCLUDED ON A DRAWING STAMPED BY THE ENGINEER OF RECORD.
3. SHEET S1.1; CANOPY FOUNDATION AND FRAMING PLANS: WHAT DO THE C-1 AND C-2 REFERENCES INDICATE? THERE IS NO COLUMN SCHEDULE, AND ONLY ONE COLUMN SIZE. CLARIFY.
03/30/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: March 30, 2009
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM00696 (Building Plan)


SUMMARY: Engineering Division of Development Services Department has received the building plan (T09CM00696). Engineering Division does not recommend approval of the building plan application at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan (D08-044). Please submit two copies of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan (D08-044). Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
04/02/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
04/07/2009 GERRY KOZIOL WWM REVIEW Passed
04/10/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 1715 W Irvington Rd , T09CM00696
Fuel Canopy

Electrical Plans denied for following items,

1.Provide a fixture cut for the type of fixture to be used under the canopy.
2. Provide circuitry for the fixtures under the canopy, and note panel to which they feed from.
3. Show where seals will be located on plan.


Ray T Majuta
DSD Tucson,Az
Electrical Plan Ck
520-837-4988
4-13-09
04/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide roof drainage calculations, showing the size and slope of the gutters and the slope of the horizontal roof leaders on the plans. Provide overflow protection for the roof. Reference: Section 1106.0, UPC 2006.
04/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/21/2009 ROBERT SHERRY WATER REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2009 DELMA ROBEY OUT TO CUSTOMER Completed
05/12/2009 SUE REEVES REJECT SHELF Completed