Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM00695
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/10/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Insulation installed on a suspended ceiling with removable tiles cannot be counted as part of the roof insulation. Reference: Section 502.2.1, IECC 2006 (see also note # 5 on your COMcheck envelope compliance certificate). |
| 11/10/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Install the vacuum relief valve in accordance with its listing, i.e. with no shut-off valve between the vacuum relief and the storage tank. Reference: Sections 310.4 and 608.7 2006 UPC. |
| 11/13/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 11/19/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. All the General Notes on sheet S1.1 are less than 3/32". Please adjust. 2. The 3/32" lettering height font requirement is for both upper and lower case. All the General Notes on sheet E0.2 that are lower case are less than 3/32". Please adjust. 3. A letter for deferred submittals is not included in the drawing package. Please submit a copy for file records. 4. Please submit completed Spections Inspection Certificates for approval. END OF REVIEW |
| 11/19/2009 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. As per ICC (ANSI) 117.1, Section 606, Lavatories and Sinks, the front shall be no higher than 34". Detail 1/122-1 shows the Break Room sing to be 3'-0". Please adjust. |
| 11/25/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED WASTEWATER 3RD FLOOR PCRWD/DON WILLHOLT REVIEW OF LOCATION & METHOD OF CONNECTION TO EXSISTING ON-SITE PRIVATE SEWER ON ADJACENT LOTS (EASEMENTS & JOINT SEWER MAINTENANCE AGREEMENTS) |
| 11/30/2009 | THAUSER1 | ZONING | REVIEW | Needs Review | |
| 11/30/2009 | THAUSER1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/30/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |