Review Details: RESUBMITTAL

Permit Number - T09CM00695
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2009 MARTIN BROWN FIRE REVIEW Approved
11/10/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Insulation installed on a suspended ceiling with removable tiles cannot be counted as part of the roof insulation. Reference: Section 502.2.1, IECC 2006 (see also note # 5 on your COMcheck envelope compliance certificate).
11/10/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Install the vacuum relief valve in accordance with its listing, i.e. with no shut-off valve between the vacuum relief and the storage tank. Reference: Sections 310.4 and 608.7 2006 UPC.
11/13/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
11/19/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. All the General Notes on sheet S1.1 are less than 3/32". Please adjust.
2. The 3/32" lettering height font requirement is for both upper and lower case. All the General Notes on sheet E0.2 that are lower case are less than 3/32". Please adjust.
3. A letter for deferred submittals is not included in the drawing package. Please submit a copy for file records.
4. Please submit completed Spections Inspection Certificates for approval.
END OF REVIEW
11/19/2009 RONALD BROWN ZONING HC REVIEW Denied 1. As per ICC (ANSI) 117.1, Section 606, Lavatories and Sinks, the front shall be no higher than 34". Detail 1/122-1 shows the Break Room sing to be 3'-0". Please adjust.
11/25/2009 GERRY KOZIOL WWM REVIEW Denied NEED WASTEWATER 3RD FLOOR PCRWD/DON WILLHOLT REVIEW OF LOCATION & METHOD OF CONNECTION TO EXSISTING ON-SITE PRIVATE SEWER ON ADJACENT LOTS (EASEMENTS & JOINT SEWER MAINTENANCE AGREEMENTS)
11/30/2009 THAUSER1 ZONING REVIEW Needs Review
11/30/2009 THAUSER1 ELECTRICAL-COMMERCIAL REVIEW Needs Review