Permit Number: T09CM00695
Parcel: 11204370H

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM00695
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2009 DAVE MANN FIRE REVIEW Approved
08/26/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Karama Offices
T09CM00695
Site Plan (2nd Review)

TRANSMITTAL DATE: August 26, 2009

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. Zoning was not able to locate the last approved site that you stated was supplied. As this site (the church, Wintrode office & proposed office) work as a single site provide a copy of the last approved site plan for the entire site.

3. D.S. 2-02.2.1.A.8 The six (6) vehicle parking spaces shown along the north side of the proposed office building will require wheel stops to prevent parking vehicle from overhanging the sidewalk.

4. Provide documentation from COT Transportation stating that there will be no intersection widening. D.S. 2-02.2.1.A.19 It does not appear that the future right-of-way (ROW) is shown correctly. Per the MS&R map the intersection widening width is 130'

5. The existing ingress/egress parking & pedestrian easement will need to be modified to include the entire PAAL located south of the Wintrode Office. This comment must be addressed prior to approval of this site plan. D.S. 2-02.2.1.A.20 The sidewalk shown along the west side of the Wintrode Office building is part of the required continuous pedestrian circulation /accessible route a pedestrian access easement is required to allow access to and from the proposed office building.

6. See comment 4 above. D.S. 2-02.2.1.A.21 Show the location of future curb along Fort Lowell Road.

7. This comment was not addressed correctly. As a Religious Use in a C-1 zone has a development designator of "28" and an office use has a development designator of "29" the calculation must be based on the individual development designators. As there are three (3) parcels each FAR must be provided for each parcel. D.S. 2-02.2.A Per D.S. 2-02.2.B When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. This said until the calculation are revised to meet this requirement Zoning cannot verify that calculation are correct. Zoning will review the calculation on the next submittal.

8. Depending on how the above comments are addressed addition comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t09cm00695

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
08/27/2009 RONALD BROWN ZONING HC REVIEW Approved
08/27/2009 ANDREW CONNOR LANDSCAPE REVIEW Needs Review 1. Submit the last approved site & landscape plans for reference. Plans were not included with submittal.

2. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.
08/28/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/08/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: September 8, 2009
SUBJECT: Site
TO: Jeffrey A Stanley
LOCATION: 3038 E Ft. Lowell, T13S, R14E, Section 32, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T09CM00695 (Second Review)


RESUBMITTAL REQUIRED: Site Plan, Drainage Report

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan and drainage report for the above referenced property. Engineering Division does not recommend approval of the site plan or drainage report at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the site plan and drainage report.

Site Plan:

1. Complied
2. Complied
3. Complied
4. Complied
5. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15. Include the line used to identify the limits of the 100-Year floodplain in the legend.

Note: All current FIRM panels are on NGVD1929. It has been noted that entire site is impacted by FEMA Zone AE. Please extend water surface elevations on site plan to extend pass property boundaries.

6. Complied
7. Complied
8. Complied
9. Complied
10. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.

Note: Provide documentation from COT Transportation stating that there will be no intersection widening. D.S. 2-02.2.1.A.19 It does not appear that the future right-of-way (ROW) is shown correctly. Per the MS&R map the intersection widening width is 130'.

11. Complied
12. Complied
13. DS Sec.2-02.2.1.A.19: Label the future sidewalk and curb area on the site plan to verify that all improvements are located outside of the future ROW.
14. Verify that all easements of record have been graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.

Note: Standard Comment will remain until plans have been approved.

15. Complied
16. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.

Note: Verify that topo lines, Finished Floor Elevations and FEMA information are all on same datum.
17. Verify that all fences, walls, or vegetation for screening and sight visibility are indicated on site plan by type, material, height, location and spacing per D.S. 2-02.2.1.27.

Note: Add note on plans indicating that every other block on wall will be left out as indicated in response to note 8..

18. Complied
19. Complied
20. Complied
21. Complied
22. Complied
23. Complied
24. D.S. 2-02.2.1.A.20 The sidewalk shown along the west side of the Wintrode Office building is part of the required continuous pedestrian circulation /accessible route a pedestrian access easement is required to allow access to and from the proposed office building.

Note: The existing ingress/egress parking & pedestrian easement will need to be modified to include the entire PAAL located south of the Wintrode Office prior to approval.

25. D.S. 2-02.2.1.A.21 Show the location of future curb along Fort Lowell Road
26. Additional comments may be forthcoming.

Drainage Report:

1. Complied
2. Complied
3. Complied
4. Indicate in drainage report and on site plan how the proposed rip rap is tied into existing rip rap or provide protection on upstream and downstream side of property.
5. Additional comments may be forthcoming.


If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2009 CPIERCE1 OUT TO CUSTOMER Completed
10/01/2009 SUE REEVES REJECT SHELF Completed