Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Tucson Water limits the demand on a 1-1/2" meter to 50 GPM. Contact Fred Coy of Tucson Water (837-2220) for approval to use a 1-1/2" meter for a demand of 59 GPM.
2. Where does key note # 10 occur on the plans? Reference: Section 103.2.3, UPC 2006.
3. Revise riser diagram A to show the trap arm for the clothes washer standpipe entering below the trap arm for the lavatory. Reference: Sections 804.1 and 908.2, UPC 2006.
4. Show how riser diagrams C and D are related. Reference: Sections 103.2.3 and 804.1 UPC 2006.
5. Provide pressure-absorbing devices for the water connections to the clothes washer. Reference: Section 609.10, UPC 2006.
12/18/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved