Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM00657
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Tucson Water limits the demand on a 1-1/2" meter to 50 GPM. Contact Fred Coy of Tucson Water (837-2220) for approval to use a 1-1/2" meter for a demand of 59 GPM. 2. Where does key note # 10 occur on the plans? Reference: Section 103.2.3, UPC 2006. 3. Revise riser diagram A to show the trap arm for the clothes washer standpipe entering below the trap arm for the lavatory. Reference: Sections 804.1 and 908.2, UPC 2006. 4. Show how riser diagrams C and D are related. Reference: Sections 103.2.3 and 804.1 UPC 2006. 5. Provide pressure-absorbing devices for the water connections to the clothes washer. Reference: Section 609.10, UPC 2006. |
| 12/18/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/22/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 12/22/2009 | SUE REEVES | REJECT SHELF | Completed |